• If the distance between the energy storage system
and the ceiling or an object above the system
is less than 500 mm,
the ceiling or structural surface above the system must be
made of non-combustible material within a radius of 600 mm
around the system.
• The system must be mounted so that the highest point
is not more than 2.2 m above the ground.
• For outdoor installation, a shelter must be installed above
the energy storage system.
Installation sketch (example: system with 6 battery modules)
Rain cover or ceiling / upper boundary
≥ 60 cm
30
- 40
cm
54 cm
Min. space required for installation
according to the number of battery modules included in the system
with side-by-side arrangement if applicable
2 battery modules:
4 battery modules:
6 - 8 battery modules:
Height data including stand plate (H 5 cm)
≥ 50 cm
30-
40
cm
54 cm
54 cm
H 251 cm × B 174 cm × T 87 cm
H 251 cm × B 258 cm × T 87 cm
H 251 cm × B 342 cm × T 87 cm
Mounting the System
≥ 60 cm
≥ 60 cm
24 cm
27 cm
107