In general, a distance to the wall of at least 50 mm must be main-
tained. For safety reasons and for the purposes of fire protection,
larger clearance distances must be ensured for walls needing pro-
tection or for combustible construction materials.
A minimum distance of 150 mm (Fig. 9a) is to be maintained be-
tween construction materials, furniture, decoration or curtains to
the rear of the stove. If the stove is rotatable, a minimum distance
of 390 mm to the rear (Fig. 9b) is to be maintained to guarantee
sufficient thermal protection! If wall coverings made out of com-
bustible materials and without thermal radiation protection have
been fitted, the clearance distance to the side is to be increased
from 390 mm to 775 mm (Fig. 9b). No combustible objects may be
placed within a distance of 500 mm above the fireplace.
No combustible construction components, furniture, curtains or
decoration may be placed within a distance of 800 mm of the fire-
box door in the thermal radiation field (Fig. 9a – 9d). This distance
can be reduced to 400 mm when a radiation protection plate venti-
lated on both sides is installed between the fireplace and the com-
bustible construction elements.
If the stove is assembled as shown in figure 9c, a minimum clear-
ance distance of 150 mm is to be maintained at the sides. If wall
coverings made out of combustible materials and without thermal
radiation protection have been fitted, the clearance distance to the
side is to be increased from 150 mm to 316 mm.
If the stove is assembled as shown in figure 9d, a minimum clear-
ance distance to the rear of 150 mm and to the side of 386 mm
must be maintained. If wall coverings made out of combustible ma-
terials and without thermal radiation protection have been fitted,
the clearance distance to the side is to be increased from 386 mm
to 775 mm.
FOR FLOOR COVERINGS NEAR TO THE STOVE:
Floor coverings made out of combustible materials in front of the
firebox opening of your PIU are to be protected with a covering
made out of non-combustible construction materials. The covering
must extend at the front by at least 500 mm and at each side by at
least 500 mm (Fig. 9d) (measured from the firebox opening or the
glass panel)!
The minimum clearance distances to combustible construction ma-
terials and furniture are provided on the stove type plate and the
clearance distances may not fall below these levels.
Wallpaper as a wall covering is not classed as combustible con-
struction materials according to DIN 4102-1.
Observe the minimum clearance distance from the chimney flue pipes
to the combustible construction materials (see 2.2.5 Flue pipes).
GB 24