Installation and assembly
Tab. 14: The supported sensors are defined as follows:
0 ... 20 l/min
Flow rate
-•
(pulses)
(*): The customer's scale can be defined between 0 ... 2000 (l/min, l/h or m
4.3.5.6
Connection of a tank base, a flow or another sensor or an R.I.C. (Remote Input Control)
4.3.5.7
Connection of a flow switch sensor to DI2:
32
0 ... 50 l/min
0 ... 200 l/min
-•
Fig. 21: Connection of a tank base, a flow or another sensor or an
R.I.C. (Remote Input Control)
1
Contact
1.
Use a two-core cable.
2.
Connect a sensor core to connector DI1 (SW) (20).
3.
Connect the other sensor core to the connector DI1 (minus)
(21).
4.
Tighten the cable gland to form a seal.
Fig. 22: Connection of a flow switch sensor to DI2
1.
Remove the protective sleeve of the cable.
2.
Strip away 7 mm of the insulation on the cores.
3.
Guide the cable through the cable gland.
4.
Connect the brown core to DI2 (plus) (33).
5.
Connect the blue power core to DI2 (minus) (35).
6.
Connect the black core to DI2 (SW) (34).
7.
Tighten the cable gland to form a seal.
0 ... 10 m
3
/h
-•
3
/h) in 4...20 mA or pulse input.
1
Customer*
-•
A3004
A3006