Installation and assembly

4.3.5 Measuring input connections

4.3.5.1
The device has 10 inputs
Tab. 6: The supported sensors are defined as follows (pH):
pH value (input PI1 or PI2)
(*): The customer's scale can be defined between -1 ... 15 pH.
Tab. 7: The supported sensors are defined as follows (ORP):
ORP value (input PI1 or PI2)
(*): The customer's scale can be defined between -1000 ... 1000 mV.
Connecting the sensors
Connecting the sensor to PI1:
Connecting the sensor to PI2:
4.3.5.2
Isolated analogue inputs 4 ... 20 mA AI1 & AI2
28
The device has 10 inputs:
2 potentiometric inputs PI1 & PI2 for pH and ORP sensors,
n
2 inputs AI1 & AI2, 4 ... 20 mA, isolated for temperature,
n
chlorine or bromine measurement,
2 inputs AI3 & AI4, 4 ... 20 mA, non-isolated for temperature,
n
chlorine or bromine measurement,
4 digital inputs DI1 ... DI4 for sensors.
n
Fig. 16: a) Potentiometric inputs PI1 & PI2
The controller has two potentiometric inputs to which a pH or ORP
sensor can be connected.
pH value 1...12
-•
0...1000 mV
-•
1.
Use a coaxial cable.
2.
Connect the cable core to the connector Pot (1).
3.
Connect the shield to the connector Ref (2).
4.
Tighten the cable gland to form a seal.
5.
Use a coaxial cable.
6.
Connect the cable core to the connector Pot (3).
7.
Connect the shield to the connector Ref (4).
8.
Tighten the cable gland to form a seal.
Fig. 17: b) Isolated analogue inputs 4 ... 20 mA AI1 & AI2
The device has 2 isolated analogue inputs 4 ... 20 mA, to which a
chlorine, bromine, ozone, hydrogen peroxide, peracetic acid, dis‐
solved oxygen or PHMB sensor can be connected.
pH value 0...14
Customer*
-•
-•
+/- 1000 mV
Customer*
-•
-•
A2998
A2999