Fault detection and elimination
8
Fault messages
Error messages at the keypad or in the parameter setting program Global Drive
Control
1)
Keypad
PC
Error
0
No fault
n n n n o o o o e e e e r r r r
71
71
System fault
System fault
c c c c c c c c r r r r
c c c c c c c c r r r r
a
61
Communication fault to
c c c c e e e e 0 0 0 0
AIF
a
(configurable in C0126)
62
Communication fault to
c c c c e e e e 1 1 1 1
CAN-IN1 with Sync
a
control
63
Communication error to
c c c c e e e e 2 2 2 2
CAN-IN2
a
64
Communication error to
c c c c e e e e 3 3 3 3
CAN-IN1 with event or
a
time control
65
BUS-OFF
c c c c e e e e 4 4 4 4
(many communication
a
faults occurred)
66
CAN Time-Out
c c c c e e e e 5 5 5 5
(configurable in C0126)
a
67
Function module
c c c c e e e e 6 6 6 6
system bus (CAN) on
a
FIF has set "Warning"
or "BUS-OFF"
(configurable in C0126)
150
Cause
-
Strong interferences on control cables Shield control cables
Ground or earth loops in the wiring
Faulty transmission of control
commands via AIF
CAN-IN1 object receives faulty data or
communication is interrupted
CAN-IN2 object receives faulty data or
communication is interrupted
CAN-IN1 object receives faulty data or
communication is interrupted
Controller has received too many
incorrect telegrams via the system
bus and has been disconnected
For remote parameter setting via
system bus (C0370):
Slave does not answer.
Communication monitoring time
exceeded.
For operation with module in FIF:
Internal fault
CAN controller sets "Warning" or "BUS
OFF"
EDK82EV113 DE/EN/FR 5.0
Remedy
-
Insert the communication module into the
hand terminal
Plug-in connection - bus module
l
Check FIF
Check transmitter
l
Increase monitoring time under C0357/1
l
if necessary
Plug-in connection - bus module
l
Check FIF
Check transmitter
l
Increase monitoring time under C0357/2
l
if necessary
Plug-in connection - bus module
l
Check FIF
Check transmitter
l
Increase monitoring time under C0357/3
l
if necessary
Check whether bus terminator available
l
Check screen contact of the cables
l
Check PE connection
l
Check bus load, if necessary, reduce the
l
baud rate
Check system bus wiring
l
Check system bus configuration
l
Contact Lenze
Check whether bus terminator available
l
Check screen contact of the cables
l
Check PE connection
l
Check bus load, if necessary, reduce the
l
baud rate
ó
ó
ó