Show/Hide Bookmarks
Code
No.
Name
C0034*
Setpoint
selection range
v
Application I/O
(A)
u u u u S S S S E E E E r r r r
1 X3/1U, X3/1I
2 X3/2U, X3/2I
C0037
JOG1
C0038
JOG2
C0039
JOG3
C0087
Rated motor
speed
C0088
Rated motor
current
C0089
Rated motor
frequency
C0090
Rated motor
voltage
C0091
Motor cos j
C0119
Configuration of
g
motor
t
v
v
temperature
-37-
monitoring (PTC
monitoring (PTC
input) / earth
fault detection
L
The most important codes for commissioning
Possible settings
Lenze
Selection
0
0
0
Unipolar voltage 0 ... 5 V / 0 ... 10 V
1
Bipolar voltage -10 V ... +10 V
2
Current 0 ... 20 mA
3
Current 4 ... 20 mA
4
Current 4 ... 20 mA open-circuit monitored
20.00 -650.00
30.00 -650.00
40.00 -650.00
à
300
à
0.0
50
10
à
50
à
0.40
0
0
PTC input not active
1
PTC input active,
TRIP set
2
PTC input active,
Warning set
3
PTC input not active
4
PTC input active,
TRIP set
5
PTC input active,
Warning set
EDK82EV113 DE/EN/FR 5.0
650.00 JOG = Setpoint
{0.02 Hz}
{0.02 Hz}
650.00
{0.02 Hz}
650.00
{1 rpm}
16000
{0.1 A}
650.0
{1 Hz}
960
{1 V}
500
{0.1}
Earth fault detection
active
ti
Earth fault detection
Commissioning
IMPORTANT
Observe the jumper setting of the
function module!
Minimum output frequency (C0010)
not effective
Changing the direction of rotation is
only possible with a digital signal.
Changing the direction of rotation is
only possible with a digital signal.
TRIP Sd5 if I < 4 mA
JOG
Setpoint
Additional JOG frequencies
q
Depending on the controller
à
Depending on the controller
à
0.0 ... 2.0 x rated output current of the
controller
230 V with 230 V controllers,
à
400 V with 400 V controllers
1.0
Depending on the controller
à
Signal output configuration under
g
p
g
l
C0415
C0415
If several parameter sets are used,
l
the monitoring must be separately
the monitoring must be separately
adjusted for each parameter set.
Deactivate the earth fault
Deactivate the earth fault
l
l
detection, if it has been activated
unintentionally.
unintentionally
If the earth fault detection is active,
l
the motor starts after controller
the motor starts after controller
enable with a delay of approx.40
ms.
7
ð
C0440
145