6.5.1.3 Overview "alarm and delay settings"
EMPTY DETERGENT / DELAY
(alarm delay at low detergent)
MAXIMUM METERING TIME
(metering time exceeded)
EMPTY RINSE AID / DELAY
(alarm delay at low rinse aid)
ADDITIV EMPTY / DELAY.
(alarm delay at low additiv)
DETERGENT OVERDOS. CONC.
(alarm at detergent overmetering)
DETERGENT OVERDOS.
(alarm at detergent overmetering)
DETERGENT OVERDOS. / DEL.
(alarm delay for detergent overmetering)
WASHTANK TEMPERATURE / LOW / HI
(limit values for washing temperature)
WASHTANK TEMPERATURE / LOW / HI
(alarm priority for washing temperature)
WASHTANK TEMPERATURE / DELAY
(alarm delay for washing temperature)
FINAL RINSING TEMP. / LOW / HI
(limit values for rinsing temperature)
FINAL RINSING TEMP. / LOW / HI
(alarm priority for rinsing temperature)
FINAL RINSING TEMP / DELAY
(alarm delay for rinsing temperature)
DRY ZONE TEMP. / LOW / HI
(limit values for drying temperature)
DRY ZONE TEMP. / LOW / HI
(alarm priority for drying temperature)
DRY ZONE TEMP / DELAY
(alarm delay for drying temperature)
6.5.2

Setting the alarm repeat

The following settings can be made with the ALARM REPEAT sub-menu:
1.
Switch off the alarm repeat function, i.e. set to OFF (factory setting) and
switch on the alarm repeat function and determine an alarm repeat time between
one and 999 minutes.
To set an alarm repeat time:
2. Activate the ALARM CONTROL SETUP menu in the program structure.
3. Activate the ALARM REPEAT sub-menu.
4. Enter the desired alarm repeat time by pressing one of the upper-key or down-key.
6.6

Configuration of the Time and Date Parameters

The time and date parameters can also be transmitted by the PC in connection with the
NOTE
"AquantaGet" PC software (except for the automatic summer time switching).
The following can be set with the TIME/DATE SETUP sub-menu:
1. the current time
2. the current date
3. the automatic summer time switching (factory setting: ON)
417101386_AquantaControl_II.doc
Functions
Setting ranges
0 -999 sec.
10 -9999 sec.
0 -999 sec.
0 - 48 mS/cm
ACOUST/VISU/MEM
(acoustic/optical/report)
0 -999 sec.
LOW: 0 - 99°C (low. limit val.)
HI: 0 - 99°C (upper limit val.)
ACOUST/VISU/MEM
(acoustic/optical/report)
0 -999 sec.
LOW: 0 - 99°C (low. limit val.)
HI: 0 - 99°C (upper limit val.)
ACOUST/VISU/MEM
(acoustic/optical/report)
0 -999 sec.
LOW: 0 - 99°C (low. limit val.)
HI: 0 - 99°C (upper limit val.)
ACOUST/VISU/MEM
(acoustic/optical/report)
0 -999 sec.
- 75 -
Default values
(ex-works setting)
Recommended values
5 sec.
180 sec.
5 sec.
20 mS/cm
MEMORY ONLY
(only reporting)
120 sec.
LOW: 55°C (lower limit value)
HI: 70°C (upper limit value)
ACOUST/VISU/MEM
(acoustic/optical/report)
120 sec.
LOW: 70°C(lower limit value)
HI: 90°C (upper limit value)
VISU/MEM (optical/report)
120 sec.
LOW: 70°C (lower limit value)
HI: 90°C (upper limit value)
VISU/MEM (optical/report)
120 sec.
Rev. 4-2/10