7.2.4
Transformer connection (primary circuit)
7.2.5
Connection for programming terminal
X1 (V24/RS232 interface, sub D)
"
Attach the cables for U2 and V2 with aluminum brackets and always
guide the cables - if necessary - through the housing metal together
(because of inductive temperature rise).
The position of the connections is indicated in Section 7.1.1 from
page 342.
Connect terminal U2 at the inverter to connection U at the trans
"
former.
"
Connect terminal V2 at the inverter to connection V at the trans
former.
"
For master slave operation, please also refer to section 13.3 starting
on page 420.
Additional information on transformer connection (parallel connec
tion of several transformers, sensors, etc.) is provided in the manual
"MF welding transformers, Technical information" (cf. page 233).
Point-to-point connection of the programming terminal (PC/laptop
computer with BOS software for administration, diagnosis, archiving,
backup).
The optional Ethernet module can be used for networking, refer to
page 282.
Only in connection with PSI 6x00.xxx!
Connection:
at X1; sub D, 9-pole, male connector
Cable length:
max. 20 m (with recommended cable type)
Cable type:
shielded, core area min. 0.2 mm
capacitance max. 2.5 nF
(e.g.: 3 x 2 x 0.2 mm
Transmission rate:
19200 bit/sec
Parameters:
8E1 (8 data bits, even parity, 1 stop bit)
X1
1
2
RX
3
TX
4
5
GND
6
7
8
9
Male connector
Screen continuity through large-area connection to metal housing of the plug connection.
Fig. 66: Connection of programming terminal via X1
For suitable connecting cables, please refer to Section 13.1 on
page 413.