Fig. 73: Wiring example: 24V voltage distribution for master slave applications
When using master slave applications we recommend to switch on the
24 V
supply of the slave inverters first. After that switch on the 24 V
DC
supply of the master inverter (24 V
Wiring: refer to option 1 (see page 370).
Make sure to switch on the mains voltage of all inverters simultaneously
or switch on the slave inverters first.