Type 8696
Controlanddisplayelements
7.6
error messages
7.6.1
error messages in manual and auTOmaTic operating
statuses
Display
Cause of fault
LED 1 (red)
Checksum error in data memory
on
→ Data memory defective
→ The device automatically switches to an older
(possibly not current) data record.
Table 12:
Error messages in the operating statuses
7.6.2
error messages while the X.TUNE function is running
Display
Cause of fault
LED 1 (red)
No compressed air connected
on
Compressed air failure while the X.TUNE function
was running
Actuator or control system deaeration side leaking
Control system aeration side leaking
Table 13:
Error messages for the X.TUNE function
remedial action
Not possible, device defective
remedial action
Connect compressed air
Check compressed air supply
Not possible, device defective
Not possible, device defective
english