8.7.59 Limit 1 exceeded (4.4.5 - 4.4.6)
Fig. 110Limit 1 exceeded
Description
With the function, CU 352 can monitor set limits of analog values.
It will react if the values exceed the limits. Each limit can be set
as a maximum or minimum value. For each of the monitored
values, a warning limit and an alarm limit must be defined.
The function allows you to monitor two different locations in a
pump system at the same time, for instance the pressure at a
consumer and the pump's outlet pressure. This ensures that the
outlet pressure does not reach a critical value.
If the value exceeds the warning limit, a warning is given. If the
value exceeds the alarm limit, the pumps will be stopped.
You can set a delay between the detection of an exceeded limit
and the activation of a warning or an alarm. You can also set a
delay for resetting a warning or an alarm.
A warning can be reset automatically or manually.
You can set whether the system is to restart automatically after an
alarm, or if the alarm must be reset manually. Restarting can be
delayed by an adjustable time. You can also set a startup delay
ensuring that the system reaches a steady state before the
function becomes active.
Setting range
Selection of analog input for the function
Input value to be monitored
Limit type (Min. limit and Max. limit)
Warning limit
Alarm limit.
62
Setting via the operating panel
Analog inputs must be correctly set before the
function is enabled. See section
(4.3.8).
Settings > Monitoring functions > Limit 1 exceeded / Limit 2
exceeded > Go to setting of analog input.
1. Select analog input.
2. Select: Input value to be monitored. Display 4.3.8.1.1
appears.
3. Select input.
4. Press [Back].
5. Set the minimum and maximum sensor value.
6. Press [Back] x 2.
7. Select: Input value to be monitored.
8. Select input.
9. Press [Back].
10. Select:
Min. limit or Max. limit.
Set delays.
11. Press [Back].
12. Select:
Set warning limit
Enabled.
13. Set limit.
14. Select resetting: Manual or Auto.
15. Press [Back].
16. Select:
Set alarm limit
Enabled.
17. Set limit.
18. Select resetting: Manual or Auto.
19. Press [Back].
20. Select: Enabled.
Factory setting
The function is disabled.