8.6 Alarm (3)
This menu gives an overview of alarms and warnings.
You can reset alarms.
8.6.1 Alarm status (3)
Fig. 31 Alarm status
Description
A fault in the system or one of the components monitored can
cause an alarm or a warning. Besides the fault signal via the
alarm and warning signal relay and the red indicator light on CU
352, an alarm can also cause a change of operating mode, for
instance from "Normal" to "Stop". A warning only causes a fault
indication.
The table shows the possible causes of fault together with an
alarm code, and whether they result in an alarm or a warning. It
also shows to what operating mode the system will change in
case of alarm, and whether restarting of the system and resetting
of the alarm is manual or automatic.
The table also shows that the reaction to some of the fault causes
mentioned can be set in the menu "Settings". See sections
8.7.26 Soft pressure build-up (4.3.3)
functions (4.4)
to
8.7.61 Pressure relief
Water shortage
Warning
Water shortage
Alarm
Pressure high
Alarm
Warning
Pressure low
Alarm
Pressure relief
Warning
Alarm, all pumps
Alarm
Warning
External fault
Alarm
Dissimilar sensor
Warning
signals
Fault, primary
Alarm
sensor
Fault, sensor
Warning
Communication
Warning
fault
Phase failure
Warning
Undervoltage,
Warning
pump
Overvoltage,
Warning
pump
28
and
8.7.51 Monitoring
(4.4.8).
-
Man/auto
X
206
Stop
Man/auto
X
214
Stop
Man/auto
X
210
-
Man/auto
X
211
Stop
Man/auto
-
Man/auto
X
219
Stop
Auto
-
203
-
Man/auto
X
3
Stop
Man/auto
-
Auto
-
204
Stop
Auto
-
89
-
Auto
-
88
-
Auto
-
10
-
Auto
-
2
7, 40,
-
Auto
-
42, 73
-
Auto
-
32
Overload, pump
Warning
Motor
temperature too
Warning
high
Other fault, pump
Warning
Internal fault, CU
Warning
352
Internal fault, IO
Alarm
351
VFD not ready
Warning
Fault, ethernet
Warning
Warning/
Limit 1 exceeded
alarm
Warning/
Limit 2 exceeded
alarm
Pressure buildup
Warning/
fault
alarm
Pumps outside
Warning
duty range
Fault, pilot pump
Warning
Multisensor fault
Alarm
Multisensor value
Warning
exceeds limits
Signal fault,
Warning
secondary sensor
Warning
Non-return valve
fault
Alarm
48, 50,
-
Auto
-
51, 54
64, 65,
-
Auto
-
67, 70
-
Auto
-
76, 83
83,
-
Auto
-
157
72, 83,
Stop
Auto
-
157
-
Auto
-
213
231,
-
Auto
-
232
-
Man/auto
X
190
-
Man/auto
X
191
-
Man/auto
X
215
-
Man/auto
X
208
-
Auto
-
216
-
Auto
-
143
-
Auto
X
87
-
Auto
X
93
-
Man/auto
X
209
-
Man/auto
X
209