INSTALLATION POWER OUTPUTS
Safety information: Power supply must be switched off completely before
work is started on the control and connected loads.
Warning: 230 VAC
If the circulation pump is to be operated via the controller, remove the three safety
terminals from the preconnected cable and connect the cable to the circulation pump
as follows:
Green/yellow:
Earth PE
Blue:
Neutral N
Brown/black/grey:
Phase L
Please note: If the pump is not connected, the electrician should remove the cable.
Output 1-
Pumpcontrol
P1
Phase L
Neutral N
P2
Earth PE
Output 2-
Extra function
Phase L
Neutral N
P3
Earth PE
Output 3-
Aux. heating
Phase L
Neutral N
POWER SUPPLY - ELECTRICAL CONNECTION
Safety information: Power supply must be switched off completely before
work is started on the control and connected loads.
Warning: 230 VAC
Please note: The controller replaces in no way safety devices. Precautions such as frost,
scald and overpressure protection, etc., must be provided in the installation if necessary.
The controller must only be installed by a qualified electrician in accordance with standards
and/or local regulations.
The 90C controller should be wired up in the following order:
Plug the preconnected cable labelled "power supply" into a 230 V / 50 Hz socket outlet
with earthing contact.
Wiring:
Green/yellow:
Earth PE
Blue:
Neutral N
Brown:
Phase L
SET-UP
COMMISSIONING HELP / SET-UP WIZARD
The first time the controller is turned on and after the language and time are set, a query
appears as to whether you want to parametrise the controller using the commissioning
help or not. The commissioning help can also be terminated or called up again at any
time in the special functions menu 9.2. The commissioning help guides you through the
necessary basic settings in the correct order, and provides brief descriptions of each
parameter in the display.
Pressing the „esc" key takes you back to the previous value so you can look at the selec-
ted setting again or adjust it if desired. Pressing the „esc" more than once takes you back
step by step to the selection mode, thus cancelling the commissioning help.

FREE COMMISSIONING

If you decide not to use the commissioning help, you should make the necessary settings
Black
in the following sequence:
Brown
- Menu 12.
- Menu 3.
~230
Grey
- Menu 5
- Menu 8.
- Menu 9.
Blue
- Menu 4.2
Yellow/Green
Language
Time, date and operating times
Settings for heat circuit, all settings
Protective functions if necessary
Special functions if necessary
Operating mode „Manual" should be used to test the switch outputs with
the consumers connected, and to check the sensor values for plausibi-
lity. Then switch on automatic mode.
Observe the explanations for the the individual parameters on the following