Options
11.5 Supplementary circuits
11.5.18

Y60, coupling relay for binary output

Category
Supplementary circuits
Function
A binary output of the SINAMICS DCM DC Converter is provided for customers via an output
coupling relay and its isolated changeover contact. The relay is in the form of a terminal
relay, so that customers can directly connect their cables at these –XK terminals. The relay
function can be freely selected. When ordering, the use must also be specified in plain text
so that it can be included in the circuit manual (e.g.: "Drive operational"). If several output
isolating amplifiers are required, then the option should be specified several times.
Connection
Table 11- 10 Terminals –XK – connection for output coupling relay
Terminal
from -K16:11
from -K16:12
from -K16:14
Max. connectable cross-section: 2.5 mm²
When ordering additional relays by specifying option Y60 several times, the following relays
are numbered starting at -K17.
Cable routing
The cables are routed into the cabinet corresponding to the following diagrams.
246
Designation
Basis
NC contact
NO contact
Operating Instructions, 04/2015, A5E36161239/RS-AA/001
Technical data
Maximum switching voltage: 250 V AC/DC,
continuous limit current 6 A
Disconnection power (ohmic load), max 140
W at 24 V DC
1500 VA at 250 V AC
SINAMICS DCM Cabinet