L99, monitoring the temperature inside the drive cabinet

Category
Monitoring functions
Function
The temperature is monitored in two stages. The response temperature for the alarm is 5 °C
below the fault signal threshold. This is oriented to the overload capability of the converter
and results in the drive being shut down. The fault message can be deselected by making
the appropriate parameter settings.
For additional information, please refer to the operating instructions SINAMICS DCM DC
Converter in Chapter, Function descriptions/sensors for ambient and air intake temperature.
Commissioning
At p50077, the derating factor must be set for power derating as a result of increased
installation altitude (K2 according to the following table), and not the derating factor
K=K1×K2:
Table 11- 28 Derating factor
Site altitude (installation altitude)
1000 m
2000 m
3000 m
4000 m
5000 m
Notes on replacing a SINAMICS DCM in a SINAMICS DCM Cabinet
● The replacement device must have option L15 or L99
● The software version of the replacement device must be V1.3 HF1 or higher. If
necessary, update the software.
The software version can be read out of parameter r50060.
Note
If option L15 or L99 is not available or the software version is prior to V1.3 HF1, then
"Protection against thermal hazards" according to EN 61800-5-1 Section 4.2 is not
guaranteed.
EN 61800: Electric power drives with adjustable speed
Part 5-1: Safety requirements
SINAMICS DCM Cabinet
Operating Instructions, 04/2015, A5E36161239/RS-AA/001
11.7 Monitoring functions
Derating factor K2
1.0
0.9
0.8
0.7
0.6
Options
279