11.7 Monitoring functions
This option only includes monitoring the armature circuit, the fault current monitoring for the
auxiliary circuit or circuits must be realized on the plant side.
Note
For protection using a differential current monitor for shutdown, the protective conductor or
PEN conductor of the cables for the cabinet supply and motor armature circuit are
dimensioned according to DIN VDE 0100, Part 540. Line conductor cross-section according
to DIN VDE 0160. As a consequence, generally the cable cross-section can be reduced.
Connection
Table 11- 23 Terminal strip –X2 – connection for fault current relay monitor
Terminal
31
32
33
37
38
39
40
Max. connectable cross-section: 2.5 mm²
24 V DC or 230 V AC circuits can be connected at the terminals of terminal strip -X2. There
is safe electrical isolation to other circuits. For example, it is possible to connect a PLC. All
terminals of the option must be operated with the same
voltage level.
Diagnostics
For a description of messages output during operation and in the event of faults (meaning of
LEDs at = D3-F15), refer to the "Additional operating instructions" section of this
documentation package.
Cable routing
The cables are routed into the cabinet corresponding to the following diagrams.
268
Designation
18
17
19
T1
T2
R1
R2
Technical data
Signaling relay ALARM (basic)
Signaling relay ALARM (NC contact)
Signaling relay ALARM (NO contact)
External test button
External test button
External reset button (NC contact or wire jumper)
External reset button
Operating Instructions, 04/2015, A5E36161239/RS-AA/001