Herunterladen Inhalt Inhalt Diese Seite drucken

Y51, Mechanical Motor Brake - Siemens SINAMICS DCM Betriebsanleitung

Sinamics drives cabinet
Vorschau ausblenden Andere Handbücher für SINAMICS DCM:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Options
11.5 Supplementary circuits
11.5.12

Y51, mechanical motor brake

Category
Supplementary circuits
Function
Connection data: 1 AC 230 V, 50/60 Hz. Brake control is realized via SINAMICS DCM
Cabinet.
From the 1-ph. 230 V AC control voltage generated in the cabinet, a feeder to supply a
magnetic holding brake is provided via a miniature circuit breaker. The feeder is controlled
via a binary output of the SINAMICS DCM DC Converter and a contactor; the binary output
must be "high" to provide power to the brake feeder (NC contact) and therefore to release
the brake. With this option, the technical data (holding current) of the motor holding brake
must be specified in plain text.
Motorized holding brakes, other control versions or different rated voltages must be specified
as a special option X30.
Connection
Table 11- 9
Terminal
61
62
PE
Max. connectable cross-section: 2.5 mm²
Parameter assignment
p50080 is used to set whether the brake is effective as holding brake (p50080 = 1) or
operational brake (p50080 = 2).
For additional parameters, see function diagram -2750- in the List Manual.
Cable routing
The cables are routed into the cabinet corresponding to the following diagrams.
240
Terminal strip -X2 – connection for motor holding brake
Designation
-
-
-
Technical data
Feeder for the motor holding
brake, controlled 1-ph. 230 V
AC
Protective conductor
Operating Instructions, 04/2015, A5E36161239/RS-AA/001
SINAMICS DCM Cabinet

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis