11.11
Documentation
11.11.1
D19, circuit diagram prepared for motor overtemperature monitoring using a
limit value transmitter
Category
Documentation
Function
The evaluation is realized using an isolated signaling contact in the motor (order code A31
according to Catalog DA 12 · 2008, Protection and monitoring).
The customer connection is realized at the TMC terminal adapter.
Connection
Table 11- 33 Terminal strip –X2 – connection for binary motor temperature monitoring
Terminal
91
92
Max. connectable cross-section: 2.5 mm
The signal at X2.91 .92 must fulfill PELV according to DIN EN 61140.
Commissioning
See the operating instructions of the SINAMICS DCM DC converter, List Manual of the
SINAMICS DCM DC converter, operating instructions of the SINAMICS DCM Cabinet,
Chapter Signal connections (Page 85).
Parameter assignment
p50489 is parameterized corresponding to the binary input used for the specific project.
Reaction
F60028
SINAMICS DCM Cabinet
Operating Instructions, 04/2015, A5E36161239/RS-AA/001
Designation
P24S
Binary input / binary output 1
2
Options
11.11 Documentation
Technical data
External signaling contact
299