11.1.4

G20, Communication Board CBE20 left

Category
SINAMICS DCM DC Converter
Function
CBE20 PROFINET left (precondition, option G00).
The CBE20 Communication Board can be used to connect to a PROFINET IO network via
the Advanced CUD.
The SINAMICS DC MASTER then assumes the function of a PROFINET IO device in the
sense of PROFINET and offers the following functions:
● PROFINET IO device
● 100 Mbit/s full duplex
● Supports real-time classes of PROFINET IO:
● RT (Real-Time)
● Connection to control systems as PROFINET IO devices in accordance with PROFIdrive,
Specification V4.1.
● In addition to PROFIBUS (standard), PROFINET can also be used for engineering with
the STARTER commissioning tool.
● Integrated 4-port switch with four RJ45 sockets based on the PROFINET ASIC
ERTEC400. The optimum topology (line, star, tree) can therefore be configured without
additional external switches.
● The SINAMICS Link function can be used in conjunction with option S01 or S02 (memory
card).
The CBE20 is inserted in the option slot of the Advanced CUD, which is inserted in the left-
hand slot.
Connection
Information on PROFINET cables and connectors can be found in the following catalog:
Industrial Communication, Catalog IK PI, 2009 edition,
Commissioning
See the SINAMICS DCM DC Converter operating instructions
Parameter assignment
See the List Manual SINAMICS DCM.
SINAMICS DCM Cabinet
Operating Instructions, 04/2015, A5E36161239/RS-AA/001
11.1 SINAMICS DCM DC Converter
Options