Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Specifications - Siemens SINAMICS DCM Betriebsanleitung

Sinamics drives cabinet
Vorschau ausblenden Andere Handbücher für SINAMICS DCM:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Technical specifications

10.3 Technical specifications
10.3
Technical specifications
NOTICE
When the conditions differ from the above stated (cable routing, cable grouping, ambient
temperature), the following instructions for routing the cables must be taken into account:
The required cable cross-section depends on the amperage which flows through the cable.
The permissible current loading of cables is defined, for example, in DIN VDE 0276-1000
and IEC 60364-5-52. It depends partly on ambient conditions such as temperature and
partly on the type of routing. If the cables are routed individually, they will be cooled
relatively well. If several cables are routed together, they may heat each other up. Please
note the corresponding derating factors for these supplementary conditions in DIN VDE
0276-1000 and IEC 60364-5-52.
Note
With option L00 (radio interference suppression filter), the short-circuit current strength may
differ from the data provided in the following tables. See Chapter L00, radio interference
suppression filter (Page 227).
Note
For the specified line-side fusing, a higher line short-circuit current is permissible depending
on the fuse used.
SINAMICS DCM Cabinet 3-ph 400 V AC, 2Q
6RM8025-6DS22
6RM8078-6DS22
6RM8091-6DS22
6RM8093-4DS22
Table 10- 10 Technical specifications for SINAMICS DCM Cabinet 3-ph 400 V AC, 60 A to 210 A, 2Q; explanation of foot-
notes following tables.
Order number 6RM80..
Power section
Armature
rated connection voltage
Rated frequency
4)
Armature rated input current
Armature circuit short-circuit current
capability
Power loss at rated DC current (ap-
prox.)
142
6RM8028-6DS22
6RM8081-6DS22
6RM8095-4DS22
V
3-ph 400 V AC (+15 % / -20 %)
1)
Hz
50
A
49.8
2)
kA
50
W
463
6RM8031-6DS22
6RM8085-6DS22
6RM8098-4DS22
..25-6DS22
..28-6DS22
74.7
50
592
Operating Instructions, 04/2015, A5E36161239/RS-AA/001
6RM8075-6DS22
6RM8087-6DS22
..31-6DS22
..75-6DS22
104
174
50
50
691
1152
SINAMICS DCM Cabinet

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis