Input coupling relays

Four binary inputs of the SINAMICS DC MASTER Converter CU1/-X177:11...14 are
provided for the customer via input coupling relays =U1-XK-K11...-K14 for external
activation. The relays are executed as terminal relays. This means that it is possible to
connect the customer cables directly to these terminals -XK.
As standard, the coupling relays are designed for a coil control voltage of 230 V AC or, with
option C51, for 24 V DC. The function of the relays -K11 and -K14 is user defined; the relay -
K12 is assigned the ON/STOP function, the relay -K13 is assigned "controller enable".
Table 4- 11
Terminal
-K11:A1
-K11:A2
-K12:A1
-K12:A2
-K13:A1
-K13:A2
-K14:A1
-K14:A1
Max. connectable cross-section: 2.5 mm
4.10.5

Output coupling relays

One binary output of the SINAMICS DC MASTER DC Converter, CU1/-X177:20, is provided
for the customer via output coupling relay =U1-XK-K15 and its floating changeover contact.
The relay is designed as a terminal relay. This means that it is possible to connect the
customer cables directly to these terminals -XK. The function of the relay is user defined,
whereby the device fault message is preset.
With option Y60, additional output coupling replays can be ordered.
Table 4- 12
Terminal
-K15:11
-K15:12
-K15:14
Max. connectable cross-section: 2.5 mm
SINAMICS DCM Cabinet
Operating Instructions, 04/2015, A5E36161239/RS-AA/001
Terminals -XK - connection for input coupling relays
Designation
-
-
-
-
-
-
-
-
Terminals -XK - connection for output coupling relays
Designation
Basis
NC contact
NO contact
2
Technical data
SINAMICS DCM fault
Maximum switching voltage: 250 V AC/DC,
continuous limit current 6 A
Disconnection power (ohmic load), max 140
W at 24 V DC
1500 VA at 250 V AC
2
Electrical installation
4.10 Other connections
Technical data
Not assigned, for customer
230 V AC
ON/STOP
230 V AC
Controller enable signal
230 V AC
Not assigned, for customer
230 V AC
93