Description of other functions
Four input relays (electrical isolation)
230 V AC is used for activation
U1-K11
U1-K12
U1-K13
U1-K14
If the ON and operating enable commands of the SINAMICS DCM are also to run via the
bus, please note that there is an AND logic operation between each of these commands and
the function of U1-K12 and U1-K13.
E-STOP button in cabinet door
A black button is located in the control cabinet door initiates voltage disconnection of the
power outputs when it is pressed, equivalent to the OFF2 function. The SINAMICS DCM DC
Converter switches to operating state o10.3.
The button is latched mechanically when it is pressed and releases when it is pulled. No
automatic restart occurs when you pull out the button.
External buttons for remote-controlled tripping can be connected at terminals -X4:1 and -
X4:2. If there is no external button, terminals 1-2 must be jumped.
Commissioning the SINAMICS DCM DC Converter with the AOP30 advanced operator panel
The procedure is described in Chapter 8.3 of the SINAMICS DCM DC Converter Operating
Instructions.
Commissioning the SINAMICS DCM DC Converter with the STARTER commissioning tool
The procedure is described in Chapter 8.4 of the SINAMICS DCM DC Converter Operating
Instructions.
Commissioning options
Commission is required for options under certain circumstances.
The relevant instructions can be found in the descriptions of the options or the enclosed
device descriptions.
SINAMICS DCM Cabinet
Operating Instructions, 04/2015, A5E36161239/RS-AA/001
Freely available
Preassigned for ON command
Preassigned for operating enable
Freely available
Commissioning
99