08.2009
11
EU low-voltage directives
73/23/EEC and RL93/68/EEC
EU directive EMC 89/336/EEC
EU machine directive
89/392/EEC
Approval
Switching at the input
Type of cooling
Permissible ambient and cooling-
medium temperature
•
during operation
•
during storage
•
during transport
Installation altitude
Permissible humidity rating
Climatic class
Degree of pollution
Overvoltage category
Degree of protection
Class of protection
Shock protection
Radio interference suppression
•
Standard
•
Options
Interference immunity
Paint finish
Mechanical specifications
- Vibrations
During stationary use:
Constant amplitude
•
•
During transport:
•
•
- Shocks
- Drop and topple
Miscellaneous
Siemens AG
SIMOVERT MASTERDRIVES
Downloaded from
www.Manualslib.com
Technical Data
EN 50178
EN 61800-3
EN 60204-1
UL:
CSA: LR 21 927
2 switching operations per minute
Air cooling with built-in fan or
air-cooling with additional water cooling
(up to 50° C see Fig. "Derating curves")
-25° C to +70° C (-13° F to 158° F)
-25° C to +70° C (-13° F to 158° F)
≤ 1000 m above sea level (100 % load capability)
> 1000 m to 4000 m above sea level
Relative humidity
Class 3K3 to DIN IEC 721-3-3 (during operation)
Pollution degree 2 to IEC 664-1 (DIN VDE 0110. Part 1).
Moisture condensation during operation is not permissible
Category III to IEC 664-1 (DIN VDE 0110. Part 2)
IP20 to EN 60529
Class 1 to EN 536 (DIN VDE 0106. Part 1)
to EN 60204-1 and DIN VDE 0106 Part 100 (BGV A3)
to EN 61800-3
No radio interference suppression
Radio interference suppression filter for Class B1 or A1 to EN 55011
Industrial to EN 61800-3
For interior installation
to DIN IEC 68-2-6
of deflection
0.075 mm in the frequency range 10 Hz to 58 Hz
of acceleration
9.8 m/s² in the frequency range > 58 Hz to 500 Hz
of deflection
3.5 mm in the frequency range 5 Hz to 9 Hz
of acceleration
9.8 m/s² in the frequency range > 9 Hz to 500 Hz
to DIN IEC 68-2-27 / 08.89
30 g. 16 ms half-sine shock
to DIN IEC 68-2-31 / 04.84
on a surface and on a corner
The devices are ground-fault protected, short-circuit-proof and idling-
proof on the motor side
Table 11-1
Siemens Controls
6SE7087-6JD50
Operating Instructions
manuals search engine
E 145 153
0° C to +40° C ( 32° F to 104° F)
(for load capability, see Fig. "Derating curves")
≤ 95 %
≤ 85 %
General data
Technical Data
during transport and storage
during operation (moisture
condensation not permissible)
11-1