EtherCAT® data transmission and configuration
86
triggering request is cancelled. The shunt signal trigger­
ing must first be cancelled before another triggering
request can be accepted.
Parameter set selection:
Values from 1 to 32 and 64 represent a valid request/
query to the TIM-EC to load the corresponding parameter
set and to set the measurement processing to the param­
eter set. The request is carried out by the TIM-EC if the
parameter set selection is not blocked or if the working
parameter set is not currently being edited (in the web
interface).
If an invalid parameter set is selected, this is signalled
with the error flag Invalid parameter set (Bit 5 TIM-EC
parameter selection).
Parameter set loading is edge triggered, i.e. when a
change is detected, the parameter set in the TIM-EC is
read once and is active.
Parameter sets 0 and from 33 to 62 are ignored by TIM-
EC for the loading.
The Flag Byte 3/Bit 5 (parameter set cannot be selected)
is always set when the selection request by the master
and the return from TIM-EC differ.
The parameter set 63 loads the working parameter set
with the factory settings.
A3704-4.0 HBM: public