VE: Version display

FF: Fault log display

9.2 MONITOR MENU

From the main menu, by holding down simultaneously for 2 sec the keys "SET" and "-" (minus), or using the selection menu and pressing + or -, you can
access the MONITOR MENU. In this menu, by pressing the MODE key, the following values are displayed in sequence

CT: Display contrast

BK: Display brightness

TK: Backlight switch-on
time

LA: Language

TE: Dissipator temperature display

9.3 SETPOINT MENU

From the main menu, hold down simultaneously the "MODE" and "SET" keys until "SP" appears on the display (or use the selection menu pressing + or -
). The + and – keys allow you respectively to increase and decrease the plant boosting pressure. Press SET to leave this menu and return to the main
menu. The adjustment range is 1-6 bar (14-87 psi).
SP: Setting the setpoint
pressure
Setting the auxiliary
pressures
P1: Setting the auxiliary
setpoint 1
P2: Setting the auxiliary
setpoint 2
P3: Setting the auxiliary
setpoint 3
P4: Setting the auxiliary
setpoint 4
Hardware and software version with which the appliance is equipped. Hardware and softwa 5.9.0 and later, the following
also applies: on this page after the prefix S: the last 5 figures of the single serial number attributed for connectivity are
showed. The whole serial number can be viewed by pressing the "+" key.
Chronological display of the faults that have occurred during system operation.
Under the symbol FF appear two numbers x/y indicating respectively the fault displayed and the total number of faults
present; to the right of these numbers is an indication of the type of fault displayed. The + and – keys scroll through the
list of faults: pressing the – key goes back through the log and stops at the oldest fault present, pressing the + key goes
forward in the log and stops at the most recent fault. The faults are displayed in chronological order starting from the
one that appeared farthest back in time x=1 to the most recent x=y. The maximum number of faults that can be shown
is 64; when that number is reached, the log starts to overwrite the oldest ones. This item on the menu displays the list
of faults, but does not allow reset. Reset can be carried out only with the dedicated control from item RF on the
TECHNICAL ASSISTANCE MENU.
The fault log cannot be deleted with a manual reset, by switching off the appliance, or by resetting the factory values,
unless the procedure described above has been followed.
Adjusts the display contrast.
Adjusts the backlighting of the display on a scale from 0 to 100.
Sets the time that the backlight is lit since the last time a key was pressed.
Values allowed: '0' always off; from 20 sec to 10 min or 'always on'.
When the backlight is off, the first time any key is pressed has the sole effect of restoring the backlighting.
Display in one of the following languages: - Italian – English – French – German – Spanish – Dutch – Swedish –
Turkish – Slovak – Romanian – Russian - Thai
Pressure at which the plant is pressurised if there are no active auxiliary pressure regulating functions.
The device has the possibility of varying the setpoint pressure according to the status of the inputs, up to 4 auxiliary
pressures can be set for a total of 5 different setpoints. For the electrical connections refer to the control unit manual; for
the software settings see paragraph 9.6 - Setting the auxiliary point input function.
If several auxiliary functions associated with several inputs are active at the same time, the device will set the lowest
pressure of all the active ones. The auxiliary setpoints can be used only through the control unit.
Pressure at which the system is pressurised if the auxiliary setpoint function is activated on input 1.
Pressure at which the system is pressurised if the auxiliary setpoint function is activated on input 2.
Pressure at which the system is pressurised if the auxiliary setpoint function is activated on input 3.
Pressure at which the system is pressurised if the auxiliary setpoint function is activated on input 4.
The pump restarting pressure is linked not only to the set pressure (SP, P1, P2, P3, P4) but also to RP. RP expresses
the decrease in pressure, with respect to "SP" (or to an auxiliary setpoint if activated), caused by the pump starting.
For example: SP = 3,0 [bar]; RP = 0,5 [bar]; no active auxiliary setpoint function- During normal operation the system is
pressurised at 3.0 [bar].
The electropump restarts when the pressure falls below 2.5 [bar].
Setting a pressure (SP, P1, P2, P3, P4) that is too high for the pump performance may cause false water lack errors
BL; in these cases lower the set pressure.
ENGLISH
MENÙ MONITOR
SETPOINT MENU