Herunterladen Inhalt Inhalt Diese Seite drucken

Sanyo Classic PAC i serie Einbauanleitung Seite 72

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 181
10-22. Automatic Address Setting
10-22-1. Basic wiring diagram
Link wiring
N OT E
A terminal plug (black) is attached to each of the
outdoor unit control PCBs. At only one outdoor unit,
leave the terminal plug short-circuit socket on the "Yes"
side. At all the other outdoor units, change the socket
(from "Yes" to "No").
A maximum of 8 indoor units can be connected to 1 remote
controller for group control.
Automatic address setting from the outdoor unit (X, T, U
Types)
Case 1
If the power can be turned ON separately for the indoor and
outdoor units in each system, the indoor unit addresses can
be set without running the compressor.
(1) Turn on the indoor and outdoor unit power for refrigerant
system 1.
Press and hold the automatic address setting button
(black) for 1 second or longer at the outdoor unit where the
power was turned ON.
Communication for automatic address setting begins.
LED 1 and 2 on the outdoor unit control PCB blink
alternately, and turn OFF when address setting is
completed.
(2) Next, turn ON the power only at the indoor and outdoor
units in a different system. Press the automatic address
setting button (black) on the outdoor unit.
LED 1 and 2 on the outdoor unit control PCB blink
alternately, and turn OFF when address setting is
completed.
Repeat the same procedure for each system and complete
automatic address setting.
(3) Operation using the remote controller is now possible.
Case 2
If the power cannot be turned ON separately for the indoor
and outdoor units in each system:
The compressors must be run in order to automatically set
the indoor unit addresses. Therefore perform this step after
completing the refrigerant tubing work.
(1) Turn ON the power to the indoor and outdoor units in all
refrigerant systems.
When setting addresses in cooling mode
(2) Short-circuit the mode-change pin at the outdoor unit
where automatic address setting will be performed. Then
press the automatic address setting button (black).
When setting addresses in heating mode
(2) Press the automatic address setting button (black) at
the outdoor unit where automatic address setting will be
performed.
(3) LED 1 and 2 blink alternately. The compressors begin
running in Cooling (or Heating) mode. Communication for
automatic address setting begins, using the temperature
changes at the indoor units.
<All indoor units are in operating status.>
Address setting is completed when the compressors stop
and the LED indicators turn OFF. <Approximately 15
minutes is required for 1 system.>
If address setting fails, LED 1 and 2 blink simultaneously
and the alarm contents are displayed at the remote
controller.
(4) After 1 system is completed, be sure to press the
automatic address setting button (black) at the other
outdoor units to complete automatic address setting in the
Fig. 10-17
same way for each system.
(5) Operation using the remote controller is now possible.
Automatic address setting using the remote controller
Case 3
If the power can be turned ON separately for the indoor and
outdoor units in each system (indoor unit addresses can be
set without running the compressor):
Individual system automatic address setting: Display item code
"A1".
(1) Press the remote controller timer time
button simultaneously.
(Hold for 4 seconds or longer.)
(2) Then press either the temperature setting
(Confirm that the item code is "A1".)
70
<Approximately 4 – 5 minutes are
required.>
button.
button and
or

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis