Technical specifications and reports

16
Technical specifications and reports
16.1

Performance

SIZE
Radiant panels
Heating
Heating capacity (EN 14511:2018)
COP (EN 14511:2018)
ErP Space Heating Energy Class - AVERAGE climate
- W35
SCOP - MEDIUM climate - W35
ns,h - MEDIUM climate - W35
SCOP - COLD climate - W35
ns,h - COLD climate - W35
SCOP - HOT climate - W35
ns,h - HOT climate - W35
Cooling
Cooling capacity (EN 14511:2018)
EER (EN 14511:2018)
Water flow-rate
User side exchanger pressure drops
Terminal units
Heating
Heating capacity (EN 14511:2018)
COP (EN 14511:2018)
Cooling
Cooling capacity (EN 14511:2018)
EER (EN 14511:2018)
SEER_7-12
ns,c_7-12
Water flow-rate
User side exchanger pressure drops
Table 61 The Product is compliant with the ErP (Energy Related Products) European Directive. It includes the Commission delegated Regulation (EU) No
811/2013 (rated heat output ≤ 70 kW at specified reference conditions) and the Commission delegated Regulation (EU) No 813/2013 (rated
heat output ≤ 400 kW at specified reference conditions). Contains fluorinated greenhouse gases (GWP 675)
1. Entering/leaving water temperature user side 30/35 °C, Entering
external exchanger air temperature 7 °C (R.H. = 85%)
2. COP (EN 14511:2018) Heating performance coefficient. Ratio
between delivered heating capacity and power input in compliance
with EN 14511:2018. The overall power absorbed is calculated by
adding the power absorbed by the compressor + the power absorbed
by the fan - the percentage value of the fan to overcome external
pressure drop + the power absorbed by the pump - the percentage
value of the pump to overcome pressure drop outside + the power
absorbed by the auxiliary electrical circuit.
3. Entering/leaving water temperature user side 50/55 °C, Entering
external exchanger air temperature 7 °C (R.H. = 85%)
4. Entering/leaving water temperature user side 23/18 °C, Entering
external exchanger air temperature 35 °C
5. EER (EN 14511:2018) cooling performance coefficient. Ratio
between delivered cooling capacity and power input in compliance
with EN 14511:2018. The overall power absorbed is calculated by
adding the power absorbed by the compressor + the power absorbed
by the fan - the percentage value of the fan to overcome external
pressure drop + the power absorbed by the pump - the percentage
value of the pump to overcome pressure drop outside + the power
absorbed by the auxiliary electrical circuit
6. User side entering/leaving water temperature 12/7 °C, external
exchanger entering air 35°C
82
16
19
1,8
kW
25,4
30,0
1,2
4,37
4,36
7
A++
A++
9
4,41
4,36
10
%
173
172
9
3,24
3,22
10
%
127
126
9
4,26
4,32
10
%
167
170
4,8
kW
29,9
34,6
4,5
4,28
3,94
4
l/s
1,43
1,66
4
kPa
40
50
3
kW
23,1
27,7
2,3
2,55
2,41
6
kW
23,3
25,8
5,6
3,11
2,84
9
4,63
4,64
11
%
182
183
6
l/s
1,06
1,23
6
kPa
23
29
7. Seasonal Space Heating Energy Efficiency Class according to
Commission delegated Regulation (EU) No 811/2013. W = Water
outlet temperature (°C)
8. Data referred to unit operation with inverter frequency optimized for
this application
9. Data calculated according to the EN 14825:2016 Regulation
10.Seasonal energy efficiency in heating EN 14825:2018
11.Seasonal energy efficiency in cooling EN 14825:2018
24
31
36
35,8
50,0
54,2
4,09
4,41
4,22
A++
A++
A++
4,31
4,33
4,33
169
170
170
3,18
3,24
3,19
124
126
125
4,31
3,81
3,82
169
149
150
38,9
59,1
65,7
3,62
4,07
3,67
1,86
2,76
3,15
63
37
49
32,6
46,5
51,9
2,33
2,70
2,68
29,3
42,5
48,2
2,78
3,02
2,95
4,63
4,00
3,99
182
157
157
1,39
2,01
2,29
41
28
32
CS3000 AWP – 6721852570 (2022/11)
41
62,2
4,03
A++
4,28
168
3,16
124
3,85
151
77,7
3,35
3,61
62
56,7
2,70
55,0
2,75
4,01
157
2,63
36