Victaulic Connections - Bosch CS 3000 AWP Installations- Und Bedienungsanleitung

Luft-wasser-wärmepumpe
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
1
2
3
T
4
9
Fig. 75 Unit + 3-way valve for domestic hot water
1. Exchanger
2. Antifreeze heater
3. Water temperature probe
4. Drain
5. Water flow switch
6. Vent
7. System loading safety pressure switch
CS3000 AWP – 6721852570 (2022/11)
T
F
5
6
7
8
17
17 B
11
12
13
14
15
16
0010044570-001
8. Pump
9. Safety valve
10.Storage tank
11.Shut-off valves
12.Filter
13.Flexible couplings
14.Piping supports
15.Exchanger chemical cleaning bypass
16.System cleaning bypass
17.Domestic hot water valve (CS AWP 16-24 and 31-41)
17B. Domestic hot water valve (CS AWP 53-59)
5.5

Victaulic connections

▶ Remove the supplied connection union by acting on the connection
joint;
▶ Weld the union to the installation pipe;
▶ Perform the connection between the installation pipe and the
evaporator, using the joint.
Do not weld the system pipe with the victaulic connection joint. The
rubber gasket might be irreparably damaged.
Fig. 76 Victaulic connection with: connection union, joint and
connection joint (parts from left to right)
Operation sequence
Before starting the unit pump, consider the following steps:
▶ Close all vents in the high points of the water circuit of the unit;
▶ Close all drain shut-off valves in the low points of the water circuit of
the units:
– Exchangers
– Pumps
– Collectors
– Storage tanks
▶ Carefully wash the system with clean water: use the bypass to exclude
the exchanger from the flow (see diagram on Domestic hot water Topic)
fill and drain the system several times;
▶ Apply additives to prevent corrosion, fouling, formation of mud and
algae;
▶ Fill the system (do not use the unit pump);
▶ Conduct a leak test;
▶ Isolate the pipes to avoid heat dispersion and formation of
condensation;
▶ Leave various service points free (wells, vents, etc.).
Neglecting to wash the filter, will lead to a more frequent cleaning
process, and it may damage the exchangers and compressors.
Water systems and pipework
0010045069-001
55