6.2

Advanced remote control board

APR
CN9
CN9
CN10 CN10
CN4
CN4
CN5
H1
H2
E'
E'
1
2
1
Fig. 81 Advanced remote control board
SA4
SA5
SA6
SA7
SA8
SA12
SA13
SA14
SA15
SA16
SA17
SA18
SA19
SA20
SA21
SA22
BMS
Table 45
6.3

Domestic hot water

Domestic hot water management is of priority compared to the system.
In DHW production mode, the compressors start only if the DHW storage
temperature is above a minimum threshold.
The maximum supply temperature threshold of the system is variable
based on the outdoor temperature.
To prevent it from falling below the minimum temperature, it is advisable
to install a backup electric heater on the DHW storage.
Outdoor
T5 DHW storage
temperature t0
tanks
to <= 30ºC
<15ºC
to <= 30ºC
>=15ºC
to > 30ºC
<20ºC
to > 30ºC
>=20ºC
Table 46 Outdoor temperature t0
The following components are required:
• 3-way valve SV1
• Temperature probe Taf1 antifreeze protection for domestic hot water
• Temperature probe T5 regulation and switching between system and
DHW production
CS3000 AWP – 6721852570 (2022/11)
CN5
CN6
CN6
CN7
CN7
CN8
CN8
CN12 CN12
1
2
1
2
1
2
2
GND 0-10V
4...20mA
ON/OFF
C/H
DHW
D-S-P
SILENT
DHW 4...20mA
DH 0 - 10V
Heat-Set 0 - 10V
Heat-Set 4...20mA
Cool-Set 4...20mA
Cool-Set 0 -10V
DL 4...20mA
DL 0 -10V
E_Gas Boiler
EVU
S-G
Customer BMS
Backup
Compr.
heater
OFF
ON
ON
OFF
OFF
ON
ON
OFF
CN13 CN13
CN14 CN14
CN15 CN15
CN16 CN16
CN17 CN17
GND
GND
0-10V
GND
GND
0-10V
4...20mA
4...20mA
Fig. 82
Operations sequence:
1. Disconnect the probe Taf1 supplied and connected as standard on
the unit (main board-CN69).
2. Connect the probe Taf1 supplied as spare part with the 10mt cable
(main board-CN69).
3. After connecting the cable put the probe on the domestic hot water line.
4. Connect T5 connector and put the T5 probe on the domestic hot
water storage.
Taf1
Fig. 83
Electrical connections
CN18 CN18
CN19 CN19
CN20 CN20
CN21 CN21
1
2
1
2
GND
0-10V
GND
0-10V
GND
0010045636-001
XT1
V2
NO
NC
N
SV1
MAIN BOARD
8.8.8.8.
ENC2
ON
S6
POWER
DSP1
DSP2
ENC4
ON
ON
S5
S12
NET_ADDRESS
CN22 CN22
1
2
0010045075-001
0
0
0010045076-001