80 | Commissioning report
Procedures
3. Inspect the air filter at the air
inlet of the operating area
4. Measure the size of the air inlet
in the operating area per device
5. Measure the size of the air outlet
in the operating area per device
6. Check the installation of the fan
set
7. Measure the distance between
the fan attachment and the ceiling
or obstacles such as cable guides
or lights
8. Inspect the top of the device
9. Remove any foreign objects
from inside the device
10. Check the markings (locking
paint) on the screw connections
11. Check that electrical
connections are tight
12. Check the tightening torque of
the terminal blocks
13. Inspect the cable strain relief
14. Check the series fuse for the
auxiliary power supply
BPT-C 200, 300, 350 | Operating manual
Desired result
Filter clean: Class G3 or G4 filter
used
Compare with the ventilation
design
In order to prevent a 'short circuit'
between the two different air
flows, fresh air and exhaust air
must be structurally separated.
Compare with the ventilation
design
In order to prevent a 'short circuit'
between the two different air
flows, fresh air and exhaust air
must be structurally separated.
Fan set is screwed into place.
Connector plugged in.
Distance at least 100 mm
No foreign objects on the device
Device does not contain any
foreign objects such as an earthing
harness, jumpers, tools or
measuring equipment
The electrical screw connections of
the power circuit were marked
during manufacturing. This makes
it easy to recognise if one of these
connections has become loose.
Cables and lines are connected
tightly.
M12 = 93 Nm
All connection cables must be
secured using cable strain relief
(cable support rail).
16 A, type B or similar
Actual result/assessment
English
Action in case of non-compliance
– Clean the air filter
– Replace the air filter
– Enlarge the air inlet
– Separate the fresh air and exhaust
air structurally
– Enlarge the air outlet
– Separate the fresh air and exhaust
air structurally
– Install the fan set
– Change the installation position of
the device. The top of the device
must remain unobstructed, to
allow air to escape.
– Remove foreign objects. The top
of the device must remain
unobstructed, to allow air to
escape.
– Remove foreign objects
– If any of the device's screw
connections are loose: Contact
the manufacturer (contact details
on the back of the manual).
– Do not commission the device
– With spring-loaded terminals,
ensure that the cables are fully
inserted
– Only handle cable lugs with
approved press tools or crimp
tools
– Correct the tightening torque
– Secure all connection cables with
a cable strain relief.
– Replace series fuses
Bosch Power Tec GmbH