40 | Installation location
BPT-C 200, 300, 350 | Operating manual
1000 m3/h
4.4:
Air flow: Required supply air
[1]
Cold supply air
[2]
Warm exhaust air
Please note the following here:
Both cabinet parts require cold supply air.
Installation
Required flow rate
On raised floors
3
4000 m
/h
On the floor
3
4000 m
/h
Requirements for the air in the operating area
To filter the supply air, use a class G3 or G4 air filter (EN 779).
Free of combustible, explosive, aggressive, caustic or corrosive gases,
vapours or dusts.
Maximum relative humidity: 95% (non-condensing)
(2)
3000 m3/h
(1)
Note
– Device takes in air from below.
– Fitted base panels guide air from the bottom
upwards.
– Device takes in air from the front and from the
side.
– All base panels must be removed.
– Protection type drops to IP 00. No more
protection against accidental contact.
– Label the operating area accordingly