54 | Installation
Only one DC main cable
CAUTION
BPT-C 200, 300, 350 | Operating manual
If you only wish to connect one main DC cable, for example because you
have installed an external switch box between the solar generator and
the central inverter:
Fit DC busbars (optionally included in the scope of delivery)
4. Connect cables at connection bar DC- and DC+.
5. Label the cables
Risk of injury due to damaged cable strain relief
Connection cables that are not strain-relieved may become damaged or
severed. This can result in serious personal injury or material damage.
Fit cable strain relief on-site
Use cable strain relief (cable support rail) to adequately secure
connection cables that enter the device
Only use aluminium or plastic cable clips for the cable strain relief. Check
all cable leads before connecting the cabling
6. Secure the cables on the cable support rails
7. Fit the protective cover and screw into place
The solar generator is connected.
5.5

Connecting to the grid

Materials required
AC cable available in accordance with regulations (AC side, p. 43)(two AC
cables can be connected per phase.)
M12 cable lug
Please note the following here:
– Cable lugs must be of the correct size for the cable cross-sections used.
– Cable lugs must be insulated on the shaft using an insulating sleeve or
shrink tubing.
– Cable lug manufacturer's specifications
Permissible tools for crimping cable lugs.
Please note the following here:
– Local regulations
– Applicable standards and directives
Prerequisites
Safety equipment installed (Required on site, p. 19)
Ensure that the AC cables are fully de-energised
IT grid available (IT grid, p. 44)(Central inverters are designed for grid
connection to a medium-voltage transformer and may only be operated in
IT (Isolé Terre) grids.)
Insulation and earth fault monitoring of the IT grid available. In the event
of an earth fault, the monitoring system must switch the device off.
Option 1: Use a medium-voltage transformer
Or option 2: Use a shared medium-voltage transformer with galvanically
isolated low-voltage coils.