18 | Safety
DC circuit breaker
Protection range
AC side
Auxiliary power supply
DC side
BPT-C 200, 300, 350 | Operating manual
DC circuit breaker (Q1–Q4)
DC circuit breakers have 2 independent trigger mechanisms:
Short-circuit protection: Fast, magnetic triggering in the event of a short
circuit
Setting: MIN 1250 A; Left-hand adjustment wheel
Line protection: Thermal triggering in the event of overload
Setting range: 175–250 A: Right-hand adjustment wheel
Standard setting: MAX 250 A
If the DC current is less than the maximum permissible input current
(Technical specifications, p. 83), the triggering threshold of the circuit
breaker on the right-hand adjustment wheel can be changed. This
adjustment can, for example, be used when a small cable cross-section is
being used. The trigger current of the DC circuit breaker can then be
adapted to the permissible continuous current of the connected cables.
When making adjustments using the right-hand adjustment wheel, please
note the following:
The ambient temperatures of the cables
The ambient temperature of the DC circuit breaker
The cabling layout
The desired voltage drop
Type of conductor (e.g. copper or aluminium)
Type of cable (e.g. earth cable)
Standards and local regulations
The specified trigger currents relate to an ambient temperature of the
circuit breaker of 40 °C. If the central inverter is ventilated adequately, the
ambient temperature of the circuit breaker will be a maximum of 10 °C
above the supply air temperature of the central inverter.
Supply air temperature
of the central inverter
[°C]
approx. 30
approx. 40
approx. 50
approx. 60
To ensure reliable and smooth operation of the central inverter, the
manufacturer recommends using the values for an ambient temperature of
+50 °C.
If you are using the optional DC busbars (Starting the device, p. 66): Set the
right-hand adjustment wheel to 250 A.
Overvoltage protection devices
Overvoltage protection
Type I and type II
Type II and type III
Type I and type II
Ambient temperature of
DC circuit breaker [°C]
MIN
40
175
50
168
60
160
70
150
Rated discharge capacity
7.5 kA, pulse of 10/350 μs
20 kA, pulse of 8/20 μs
7.5 kA, pulse of 10/350 μs
English
Trigger current [A]
MED
MAX
212.5
250
204
240
195
230
185
220
Bosch Power Tec GmbH