CONNECTING REQUIREMENT
For SDC07*3E5/SDC09*3E5
The equipment's power supply 1 complies with IEC/EN 61000-3-12.
The equipment's power supply 1 complies with IEC/EN 61000-3-3
and can be connected to current supply network.
The equipment's power supply 2 complies with IEC/EN 61000-3-2.
The equipment's power supply 2 complies with IEC/EN 61000-3-11
and shall be connected to suitable supply network, with the following
maximum permissible system impedance Z
interface. Please liaise with supply authority to ensure that the power
supply 2 is connected only to a supply of that impedance or less.
INSTALLATION OF REMOTE
7
CONTROLLER AS ROOM
THERMOSTAT
Remote Controller 3 mounted to the Indoor Unit can be moved to
the room and serve as Room Thermostat.
Installation Location
Install at the height of 1 to 1.5 m from the fl oor (Location where
average room temperature can be detected).
Install vertically against the wall.
Avoid the following locations for installation.
1. By the window, etc. exposed to direct sunlight or direct air.
2. In the shadow or backside of objects deviated from the room
airfl ow.
3. Location where condensation occurs (The Remote Controller
is not moisture proof or drip proof.)
4. Location near heat source.
5. Uneven surface.
Keep distance of 1 m or more from the TV, radio and PC. (Cause
of fuzzy image or noise)
Remote Controller Wiring
Indoor unit
Terminal for Remote Controller wiring
Remote Controller cable shall be (2 x min 0.3 mm²), of double
insulation PVC-sheathed or rubber sheathed cable. Total cable
length shall be 50 m or less.
Be careful not to connect cables to other terminals of Indoor Unit
(e.g. power source wiring terminal). Malfunction may occur.
Do not bundle together with the power source wiring or store in the
same metal tube. Operation error may occur.
Remove The Remote Controller From Indoor Unit
1. Remove the top case from the bottom case.
8
= 0.426 at the
max
Remote Controller
Remote Controller wiring
(fi eld supply)
No polarity
Insert the
driver and
slightly turn.
Flat-blade
screwdriver
Bottom
case
2. Remove the wiring between Remote controller and Indoor Unit
terminal. Remove the bottom case from the Control board cover
by loosening the screws. (3 pieces)
Disconnect the
Remote controller
wiring
Mounting The Remote Controller
For exposed type
Preparation: Make 2 holes for screws using a driver.
Mount the top case.
Align the claws of the top
case and then align the claws
of the bottom case.
Cut here with
a nipper and
remove the burr
with a fi le.
Claw (2 places)
1
2
Connect the remote control
wiring
Arrange the wires along the groove
of the case.
Claw
(2 places)
Mount the bottom case to
the wall.
U P
Wall to which
the remote
controller is
fi xed
Hole for screw
Claw (2 places)
Screw
(fi eld supply)
Clamper
(fi eld supply)
Pass through
the hole
Remote controller terminal board
Remove the coating. Approx. 6 mm
Top case
(Back side)
Bottom case
(Back side)
Remove the sheath. Approx. 180 mm.
Make sure the wiring connection is in the
correct direction.