TIM-PN
7.2

Shielding design

The cable shield is connected in accordance with the
Greenline concept. This encloses the measurement sys­
tem in a Faraday cage. It is important that the shield is
laid flat on the housing ground at both ends of the cable.
Any electromagnetic interference active here does not
affect the measurement signal.
In the case of interference due to potential differences
(compensating currents), operatingvoltage zero and
housing ground must be disconnected on the amplifier
and a potential equalization line established between the
stator housing and the amplifier housing (copper conduc­
2
tor, 10 mm
wire crosssection).
7.3

Pin assignment

The housing of the TIM-PN has 4 Phoenix Combicon
connector blocks, one Ethernet socket, two PROFINET
sockets and two 10+2 sockets/connectors. In delivery
condition the spring-loaded terminals are plugged into the
connector blocks.
A4341-2.0 HBM: public
Electrical connection
15