After starting the modules, the connected interface mod­
ules first have to be initialized - LED flashes red.
Super-master function
The Super-Master takes over data handling within the
setup and makes the flow of measurement data available
on the 10+2 bus. In addition to this, it is only the head-
end parameterized as the Super-Master that has full ac­
cess to the connected torque transducer. This means, for
example, that only the Super-Master can trigger the shunt
signal. All the incoming data can be scaled and filtered
separately and without reaction, for example, within the
setup (super-master/slave operation).
Slave function
It is as if the slave listens in to the flow of communication
data between the torque sensor and the Super-Master. It
behaves passively and acts solely as a listener within the
setup. All the incoming data can be scaled and filtered
separately and without reaction, for example, within the
setup (super-master/slave operation/mode).

10.3.7 Input mode

It is possible to adapt the receiving module for the TIM-
PN torque signal to the respective output signals of the
connected HBM torque transducers.
Digital signal:
S TMC
Frequency signal (mid-frequency):
S 10 kHz
S 60 kHz
S 240 kHz
TIM-PN