Settings
Failure specification
Failure display time
Manual failure
display time (in ms)
Valid range: 0 to
20000 ms
48
Failure settings
Overflow (7FFFFFFFh)
Underflow (80000000h)
Last valid value
Actual value
automatic; manual
0
If, for instance, the torque value is incorrect (e.g. actual
value > 120% of the rated value or transmission error
between rotor and stator), then the output will conform to
what you have set under error specification. If you selec­
ted Overflow, the torque value will change to 7FFFFFFFh
in the case of an error.
For how long the error should be signaled on the
PROFINET interface can be set manually, or automatic­
ally determined by the system.
If you select automatic, the error duration for dynamic
errors will be specified subject to the set filter. Static er­
rors are displayed until they are rectified.
Filter
3 kHz
1 kHz
100 Hz
10 Hz
A4341-2.0 HBM: public
Failure flag duration on PROFINET
520 μs
1.235 ms
10.9 ms
130 ms