Herunterladen Inhalt Inhalt Diese Seite drucken

HBM TIM-PN Montageanleitung Seite 74

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Settings
72
If a transducer with just one track is connected, it must be
connected to A+F1 /A-F1 and no direction of rotation will
be available.
Notice
Only external encoders with standard 5V as per the
RS422 standard may be connected.
Angle resolution
S 1x - The F1 leading edges are evaluated
S 2x - The F1 leading and trailing edges are evaluated
S 4x - The F1 and F2 leading and trailing edges are
evaluated
Max. angle
The angle can be counted from 0° to 360° or from 0° to
720°. When the end value has been reached, the angle
starts again at 0°. If the transducer outputs a quadrature
signal, the angle is counted forwards and backwards.
Angle interpolation
The angle values at the sampling instant are interpolated
between the edges of the input signals F1/F2.
Glitch filter
If double edges or interferences occur in the transducer,
these can be rectified with the aid of the glitch filter. 1μs
means for instance that no further edges are evaluated
for 1μs after an edge has been detected.
A4341-2.0 HBM: public
TIM-PN

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis