Trip Amplifier 1/209
Software Description
4.4
Numerical Parameter List
All device parameters are listed in numerical order.
4.4.1
P100 ... P299 Program and Commands
Program changes can only be undertaken with jumper MODE in the ENABLE position.
Trips are only monitored with jumper MODE DISABLE.
Parameters P100 to P299 contain up to 200 programming steps. User programs can be
entered to adapt the device to various applications. A powerful EDITOR is available for
PC users. Once edited using (F2) programs must be compiled using compiler (F3).
Direct entries via the handheld device are also possible. Enter the parameter number
followed by the desired command.
Example
Multiply analogue input 1 and 2, store result in 1
P100 = MUL <EXE>
P101 = AE1 <EXE>
P102 = AE2 <EXE>
P103 = X01 <EXE>
Available commands and operands can be taken from the following list.
4.4.1.1
Operands
AE1 ... AE4
DE1 ... DE4
SE1 ... SE4
TE1 ... TE3
X01 ... X20
K01 ... K20
Fixed values (program) and corresponding figures
Z00
0
analog inputs 1 ... 4 return up-to-date values (0 ... 1) of analog inputs (read only)
digital inputs 1 ... 4 derived from analog inputs
DEx = -1 when AEx < 33 %
DEx = 0 when AEx >= 33 % and <= 66 %
DEx = 1 when AEx > 66 %
(read only)
DIP-switches 1 ... 4 return uptodate values (0 or 1) of DIP-switches (read only)
push button inputs (1 when pressed)
push button inputs (0 when pressed)
variables 1 ... 20 read and write
constants 1 ... 20 stored in EEPROM (read only)
Z01
Z02
Z03
1
2
3
Z04
Z05
ZM1
4
5
-1
Z1H
Z1T
100
1000
73