6.3 Safety zone for 200 mm raised
installation
If the device is raised above the installation surface by 200 mm
using a strip footing or other suitable method, a safety zone
of 1 metre must be maintained all the way around the device.
There must not be any ignition sources such as sockets, light
switches, lamps, electrical switches or other permanent ignition
sources, windows doors, ventilation openings, light wells, drain-
age openings and similar in this zone. Fire loads must also be
avoided. Open drains to a lower level are permitted providing
there are no openings into the sewer system within 1 metre
Fig. 6.1:Safety zone (raised installation) around the heat pump
EN-10
1
1000
1
1000
2
800
452171.66.01-EN · FD 0212
around them. Building openings must be made airtight within
the safety zone. The safety zone must not protrude onto neigh-
bouring property or public traffic areas. The device must be po-
sitioned so that in the event of a leakage no refrigerant can get
into neighbouring buildings.
If the device is to be installed on a continuous foundation, a cut-
out in the area of the condensate outlet is recommended to
allow connection work on the condensate drain to be carried
out with no problems.
No structural modifications are to be made in the safety zone
that could violate the integrity of the safety zone.
1420
1000
1000
LA 1118CP