Installation
6.1 General
These specifications have priority during installation and opera-
tion of the system and must be complied with. The responsibil-
ity for this lies with the specialist system construction company.
The heat pump, especially its refrigeration circuit, must be pro-
tected against damage (e.g. drilling, burning etc.) during instal-
lation and other construction activities.
DANGER!
Risk of death due to fire and explosion.
If there is a leakage of the propane refrigerant due to a fault,
an ignitable atmosphere can form.
Avoid ignition sources and fire loads in the safety zone.
Keep the casing closed.
The heat pump is not an ignition source.
EN-8
DANGER!
Risk of death due to fire and explosion.
If there is a leakage of the propane refrigerant due to a fault,
an ignitable atmosphere can form, especially in hollows,
shafts or areas with no free air outflow or air exchange.
Installation in hollows, shafts or areas with no free air
outflow or air exchange is not permitted.
DANGER!
Risk of death due to fire and explosion.
In the very unlikely event that propane gets into the heating
circuit, an ignitable atmosphere can form due to mixing with
the surrounding air.
The minimum volume of the room in which the hydraulic
system - comprising the safety group, automatic air vent
and buffer - is installed must not be less than 12 m³.
NOTE
Observe country-specific building regulations.
NOTE
The responsibility for heat pump installation lies with the
specialist system construction company.
NOTE
Once the heat pump has been commissioned by an
authorised and qualified after-sales service technician, the
responsibility for the intended operation of this heat pump
lies with the operator.
NOTE
The heat pump is not intended for use above 2000 metres
(mean sea level).