X1.1/+UG, X1.1/-UG DC supply (DC-bus operation - see Operating Instructions)
Fuses and cable cross-sections
Type
Type
E82EV551K4B
E82EV751K4B
E82EV152K4B
E82EV222K4B
1)
Use UL-approved cables, fuses and fuse holders only.
UL fuse: voltage 500 ... 600 V, tripping characteristic "H" or "K5"
2)
All-current sensitive residual current circuit breaker for the use with E82EVxxxK4B00x
3)
All-current sensitive residual current circuit breaker for the use with E82EVxxxK4B20x
Observe national and regional regulations (e. g. VDE 0113, EN 60204)
Please observe the following when using e.l.c.bs:
E.l.c.bs must only be installed between mains supply and controller.
l
E.l.c.bs can trip incorrectly because of
l
– capacitive leakage currents of the cable shields during operation (especially with long,
shielded motor cables),
– simultaneous connection of several controllers to the mains supply,
– use of additional RFI filters.
L
X1.1
L1
+UG -UG
L1 L2
3/PE AC 400 V
mains
mains
Installation to EN 60204-1
Fuse
M6 A
3/PE AC
M6 A
320 ... 550 V;
M10 A
45 ... 65 Hz
M10 A
EDK82EV222 DE/EN/FR 6.0
Electrical installation
Mains connection 400 V
L3 PE
L2/N
Abb. 1-10
L3
PE
E.l.c.b.
L1, L2, L3, PE
2
[mm
B6 A
1
B6 A
1
B10 A
1.5
B10 A
1.5
X1.1
Installation to UL
Fuse
L1, L2, L3, PE
]
[AWG]
5 A
18
5 A
18
10 A
16
10 A
16
3
8200vec011
1)
FI
FI
2)
≥ 300 mA
3)
≥ 30 mA