5.1 STORING AND CLEANING OF THE SENSOR

To avoid any measurement error due to electrode soiling a regular cleaning of the elements
in contact with the medium is recommended (the cleaning frequency depends on the appli-
cation). The sensor can be cleaned with water or another cleaning agent compatible with
the PVDF, stainless steel or PEEK. Do not use abrasive products. After cleaning, always
rinse the measuring element. Before setting back into operation:
-
check the gaskets and change them if need be, as well as other damaged elements
(see section 6.7)
-
calibrate the "flow zero" point (see section 4.5.3).

5.2 TROUBLE SHOOTING GUIDE

The current output is set to 22 mA in case of an electronic failure and at the start-
up of the device all parameters are set to factory setting values (section 4.6). The
reasons for failure can be seen within "Display 'ERRORx' - output current 22mA" in
the trouble shooting guide below.
If any problems persist, please contact your local Bürkert subsidiary orre-
turn the product with a full explanation of the problem.
This section is designed to assist with problems which may occur during installation or ope-
ration. If in doubt please do not hesitate to contact you local Bürkert subsidiary
Faults
The transmitter does not work
- Transmitter connected?
- Power supply on terminal + and - ok?
- Power supply between 18-36VDC?
- Power supply regulated (Oscillations rate ≅ ±5%)?
- Fuse ok?
- Switch on?
Transmitter programming/testing unavailable
Internal switch 2 'Locked'?
Display «ERROR3» - output current 22 mA
- Display at the start-up?
- Error at each start-up?
Display «ERROR4» - output current 22 mA
- Display at the start-up?
- Error at each start-up?
Display «ERROR5» - output current 22 mA
- Display at the start-up?
- Error at each start-up?
MAINTENANCE
Status
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
34
Actions
Connect the device.
Check the connection.
Change power supply.
Change power supply
Change the fuses
Set the switch ON
Set switch 2 to 'unlock'
Press ENTER then check totalizers.
Return the device.
Press ENTER then calibrate the
device again
Return the device.
Press ENTER then check totalizers
and calibrate the device again.
Return the device.
See
3.3
3.3
--
--
--
--
3.4.1
4.3
--
4.4
--
4.3
4.4