3.2 INSTALLATION
The 8045 flow transmitter can be installed into pipes using our specially designed fitting-
system S020.
The fitting 4 must be installed into the pipe according to the installation specifications within
section 3.1.
Insert the plastic nut 3 onto the fitting 4 and snap the plastic ring 2 into the guide-bush 5.
Insert the sensor into the fitting ensuring the arrow on the side of the housing indicates
the flow direction, and:
Version with a PVDF sensor: ensuring the sensor is sitting correctly, making sure that
the lug 6 is aligned correctly onto the fitting.
Version with a stainless steel sensor: ensuring the cable glands show the downstream
direction and the alignment of the electrodes is perpendicular to the flow direction.
If the mounting is correct, the sensor housing 1 cannot be rotated.
The plastic nut must only be tightened by hand!
INSTALLATION
Flow direction
1
4
Fig. 3.1 Installation of flow transmitter
6
(PVDF Sensor)
2
3
5
10
8045