Herunterladen Diese Seite drucken

Pepperl+Fuchs ICE11-8IOL-G60L-V1D Handbuch Seite 189

Feldbusmodul mit multiprotokoll-technologie und i/o-link
Vorschau ausblenden Andere Handbücher für ICE11-8IOL-G60L-V1D:

Werbung

ICE11-8IOL-G60L-V1D
IIoT-Funktionalität
Struktur
STANDARD Object
Name
name
order-id
fw-version
hw-version
mac
bus
failsafe
ip
snMask
gw
rotarys
ulPresent
usVoltage_mv
ulVoltage_mv
inputs
output
consuming
producing
Datentyp
Beschreibung
string
Device name
string
Ordering number
string
Firmware version
string
Hardwareversion
string
MAC address of the device
number
0 = No connection
1 = Connection with PLC
number
0 = Normal operation
1 = Outputs are in failsafe
string
IP address of the device
string
Subnet Mask
string
Default gateway
array of numbers (3)
Current position of the rotary
switches:
Array element 0 = x1
Array element 1 = x10
Array element 2 = x100
boolean
True, if there is a UL voltage
supply detected within valid
range
number
US voltage supply in mV
number
UL voltage supply in mV (only
available for devices with UL
supply)
array of numbers (2)
Real state of digital inputs
Element 0 = 1 Byte: Port X1
Channel A to Port X4 Chan-
nel B
Element 0 = 1 Byte: Port X5
Channel A to Port X8 Chan-
nel B
array of numbers (2)
Real State of digitaloutputs
Element 0 =1 Byte: Port X1
Channel A to port X4 Chan-
nel B
Element 0 = 1 Byte: Port X5
Channel A to port X8 Chan-
nel B
array of numbers (2)
Cyclic data from PLC to
device
array of numbers (2)
Cyclic data from device to
PLC
Beispiel
"ICE11-8IOL-G60L-
V1D"
"70146527"
"V.1.1.0.0 -
01.01.2021"
"V.1.00"
"3C B9 A6 F3 F6 05"
1
0
\[128,3\]
\[55,8\]
189

Werbung

loading