30 RV / CPP devices settings menu (specialist installers)
30.8 Test mode
Test mode for a function test of the individual
ventilation units. The automatic dampers and fans
are tested. There are 3 test functions available
for this purpose:
• Complete test: Fan operation and damper
movement are tested at short intervals.
• Fan: Fan test without damper movement.
• Damper: Test of the integrated dampers with
continuous damper movement. When the unit is
switched off, the dampers must close the air
supply.
• Off: Cancellation of the current test run.
30.9 Changing device address
The device addresses are assigned consecutively
at the factory. This means that no address oc-
curs more than once per delivered pallet of
ventilation devices.
However, if there are 2 ventilation devices with
the same device address in a system, one of the
two addresses must be changed manually.
To do this, disconnect one of the two ventilation
devices from the RS 485 bus and reconfigure the
other devices with a different device address.
The new device address is checked.
If the check is successful, Executed appears.
Then reconnect the disconnected device to the
bus and manually reassign both devices, see
chapter Assignment [} 91].