Remote monitoring with the Smart Inspector system via Internet PC
The Smart Inspector is a web-based database system for comfortable remote monitoring of
tank data.
Also in this case, the SmartBox
received, logged and processed by the Smart Inspector server.
In case of malfunction, the SMS event messages are forwarded to the mobile phone number
indicated by the customer.
For guest access to the Smart Inspector, please go to www.smart-inspector.com.

OPERATION

The product requires no operation while it is running.

FUNCTION CHECK

We recommend that you check the displayed litre values once per year to make sure that they
are correct.
For a simple check, pull the level probe up by its cable so that it hangs above the liquid.
In this status the display device should show 0 litres (+ tolerance).
The probe signal can be checked with menu step "22. Test Current"
At 0 cm fill level  approx. 3.7 – 4.3 mA.
In the event of a considerable deviation, we recommend a replacement. New probe.
New probe/ replacement of the operating medium
If the installation of a new probe is required and/or a change in the operating medium takes
place, then firstly, all of the "standard values" under menu step "9th zero point probe" must be
reset to the factory setting!
It is also necessary to check, and if required, correct all further set values.

MAINTENANCE

See FUNCTION CHECK.

RESTORATION

If the actions described in TROUBLESHOOTING do not lead to a proper restart and if there is
no dimensioning problem, the product must be sent to the manufacturer to be checked. Our
warranty does not apply in cases of unauthorised interference.
In case of repeated errors or alarm messages (relay output) while the tank content does not
reach / remains below the set fill level alarm threshold at the probe element, check the
connection line of the signal and probe element for breakage or short-circuit, re-install if
necessary.

DISPOSAL

To protect the environment, our products may not be disposed of along with
household waste.
The product must be disposed of via a local collection station or a recycling station.