Test connector option
For testing at the test connection, we recommend the leak and function tester type DFP25
(Part no. 02 617 05).

START-UP

After ASSEMBLY and LEAK CHECK the product has been carried out successfully, it is
immediately ready for operation.
1. All shut-off fittings on the connected devices must be closed.
2. Slowly open the withdrawal valve or the gas cylinder valve.
3. Observe the assembly and operating instructions of the connected devices.
If you open the withdrawal valve or the gas cylinder valve too quickly, this can result in
a short-term pressure increase that triggers the overpressure shut-off device (OPSO).
If the visual indicator switches to RED during start up, do the following:
• Allow a few short bursts of gas to escape from the connected device to equalise the
pressure.
• If the pressure does not equalise and the OPSO cannot be unlocked
(visual indicator remains RED), the pressure regulator must be replaced.

OPERATION

The product requires no operation while it is running.

TROUBLESHOOTING

Fault cause
Gas smell
Leaking LPG is extremely
flammable.
Can cause explosions.
Abnormal flame pattern of
non-adjustable pressure
regulator
OPSO cannot be unlocked
Artikel-Nr. 05 151 50 h
A leak tester can be connected to the test connector
for pressure and leak tests. First, loosen the set
screw in the test connector. When you have used it,
tighten the set screw again and check for leaks
again. See LEAK CHECK.
Action
 Close the gas supply.
 Do not use any electric switches.
 Do not use a phone in the building.
 Ventilate rooms well.
 Shut down the LPG system.
 Contact a specialised company.
Compare the nominal outlet pressure of the pressure
regulator with the nominal inlet pressure of the connected
consuming device:
 if they do not correspond, replace the pressure regulator
or the gas appliance.
Outlet pressure is permanently too high:
 Pressure regulator is damaged, replace.