Herunterladen Inhalt Inhalt Diese Seite drucken

GOK SmartBox 4 Montage- Und Bedienungsanleitung Seite 47

Tankmanagement-systeme
Vorschau ausblenden Andere Handbücher für SmartBox 4:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Menu
Input function
4.Tank
Adjust the tank volume with [+] / [-] (100%). The default
volume
setting is 0 L. The value must be set.
5.Tank
Enter inner tank height in millimetres: e. g.: 249 cm
height
(max. value = 999,9 cm) (height without dome)
5b.Filling
Set the filling limit of the tank with [+]/ [-]:
limit
With fuel oil tanks, that is the shut-off point of the limit
indicator. The default setting is 95%.
e.g. 95%=237cm. For tanks which can be filled to the
very top (e.g. water tanks), it is necessary to set the
highest value of 99%.
6.View
In the 1st line of the display, the tank name/medium and
Tank
contents are displayed (e.g. in litres).
SmartBox 4
The display in the 2nd line can be selected:
View details
e.g.
Single/detailed
For fuel oil tanks in Germany, a free capacity display is
required according to TRwS 791-2. This is possible with
selection a) and b).
6.Show
Single/Detailed
Tanks
 SmartBox
4 PRO
Collective
Percent
Entering incorrect switching points and mixing up the switch-on and shut-off
point can lead to the overfilling of the tank or the dry running of a pump!
7.Relay 1
 SmartBox 4
part no. 28 400 57 c
Please see a volume table for the highest value,
if available. For a 100 m³ cyl. buried tank, this
may for example be the value 100600 litres.
Please see a volume table for the highest value,
if available. For a 100 m³ cyl. buried tank, this
may for example be the value 288 cm.
Yes
No
Switch function relay:
Deactive
The relay does not switch.
Active
The relay switches .
ON
Forces the relay to energise.
OFF
Forces the relay to de-energise.
Active+SMS When the relay switches over a
message is output
SmartBox
Fillspace+Percent
Fillspace+Level
Percent+Level
The tanks are displayed
cyclically one after the other, with L, % and, if
applicable, temperature. With display change.
The (e.g. L) values of tanks 1 to 4 are displayed
(depending on the number of connected probes)
Without display change.
Select Yes  display change
values (e.g. in L) Tank 1 – 4 
total capacity display + percent values
®
®
4 / SmartBox
Input value
___________L
_________mm
__________%
a)
____________
b)
c)
4 PRO