MANUALE TECNICO MT036
5.2
MESSA IN GAS, CONTROLLO
TENUTA ESTERNA E TARATURE
La
manovra
di
pressurizzazione
dell'apparecchiatura, dovrà essere fatta
molto
lentamente.
l'apparecchiatura non subisca eventuali
danni sono assolutamente da evitare:
- La
presurizzazione
attraverso
valvola
posta
dell'apparecchiatura stessa.
- La depressurizzazione attraverso una
valvola
posta
dell'apparecchiatura stessa.
La tenuta esterna è garantita quando,
cospargendo l'elemento in pressione con un
mezzo schiumogeno, non si formano
rigonfiamenti di bolle.
Il
regolatore
e
le
altre
apparecchiature (valvola di blocco, monitor)
vengono normalmente forniti già tarati al
valore richiesto. E' peraltro possibile che per
vari motivi (es. vibrazioni durante il
trasporto), le tarature possano subire
modifiche, restando in ogni caso comprese
entro i valori consentiti dalle molle utilizzate.
Si consiglia quindi di verificare le tarature
secondo le procedure di seguito illustrate.
Nelle tabelle 7 e 8 sono riportati i valori
consigliati di taratura delle apparecchiature
previste
nelle
diverse
impiantistiche. I dati di queste tabelle
possono risultare utili sia in fase di verifica
delle tarature esistenti, sia in caso di
modifiche delle stesse che dovessero
rendersi necessarie in tempi successivi.
Per gli impianti composti da due linee, si
suggerisce di procedere alla messa in
servizio di una linea alla volta, iniziando da
quella con taratura inferiore cosiddetta "di
riserva". Per questa linea, i valori di
taratura
delle
apparecchiature
scosteranno ovviamente da quelli indicati
dalle tabelle 7 e 8.
Prima di procedere alla messa in servizio
del regolatore è necessario verificare che
tutte le valvole di intercettazione (entrata,
uscita, by-pass eventuale) siano chiuse e
che il gas sia a temperatura tale da non
generare disfunzioni.
5.3
MESSA IN SERVIZIO DEL
REGOLATORE
Nel caso sia presente sulla linea anche la
valvola di sfioro, fare riferimento al
paragrafo 3.1 per la sua verifica.
TECHNICAL MANUAL MT036
5.2
GAS INPUT, CONTROL OF EXTERNAL
TIGHTNESS AND SETTING
The apparatus pressurization operation
must be carried out very slowly. To protect
Affinchè
the apparatus from damage, the following
operations must never be carried out:
- Pressurization through a valve located
una
downstream from the apparatus itself.
a
valle
- Depressurization through a valve located
upstream from the apparatus itself.
External tightness is guaranteed if no bubbles
a
monte
form when a foam medium is applied on the
element under pressure.
The regulator and any other apparatuses
(slam-shut,
supplied already set for the desired set-
point. It is possible for various reasons
eventuali
(e.g., vibration during transport) for the
settings to be changed while remaining
within the values permitted by the springs
used.
We therefore recommend checking the
settings using the procedures illustrated
below.
Tables 7 and 8 give the recommended set-
points for the apparatuses in the various
installation arrangements. The figures in
these tables can be useful both when
checking existing set-points and for
filosofie
modifying them should this become
necessary later.
In installations consisting of two lines, we
suggest commissioning one line at a time,
starting from the one with the lower set-
point, known as the "reserve" line. The set-
points of the apparatuses in this line will
obviously deviate from those specified in
the tables 7 and 8.
Before commissioning the regulator you
must check that all the on/off valves (inlet,
si
outlet, any by-pass) are closed and that the
gas is at a temperature which will not lead
to malfunction.
5.3
COMMISSIONING THE
REGULATOR
If there is also a relief valve in the line, refer
to par. 3.1 to check it.
monitor)
are
normally
40
TECHNISCHES HANDBUCH MT036
5.2
UNTER DRUCK SETZEN DER
REGELSTRECKE, KONTROLLE
DER ÄUSSEREN DICHTHEIT UND
DER EINSTELLUNGEN
Der Vorgang zum Füllen des Geräts mit Gas
muss sehr langsam erfolgen. Damit das Gerät
nicht beschädigt wird, ist Folgendes absolut zu
unterlassen:
- die Druckbeaufschlagung durch ein Ventil
in der Ausgangsleitung des Geräts,
- die Druckminderung durch ein Ventil in
der Eingangsleitung des Reglers.
Zur Prüfung der äußeren Dichtheit empfehlen
wir den Einsatz einer schaumbildenden
Substanz (Lecksucher-Spray).
Das Regelgerät und die anderen gegebenenfalls
zusätzlich benötigten Geräte (Sicherheitsab-
sperrventil,
Monitorregler)
entsprechend
der
Bestellanforderung
voreingestellt geliefert. Es ist jedoch möglich,
dass
sich
diese
Einstellungen
verschiedenen Gründen (z.B. Erschütterungen
beim Transport) verändern, wobei sie jedoch
immer in-nerhalb des Führungsbereichs der
verwendeten
Federn
bleiben.
empfehlen wir, die Einstel-lungen gemäß den
nachfolgenden Anweisungen zu überprüfen.
In den Tabellen 7 und 8 sind die empfohlenen
Einstellwerte der Geräte, so wie sie für die
verschiedenen
Anlagearten
empfohlen werden, aufgeführt. Die Daten in
diesen Tabellen können sowohl bei der
Überprüfung der bestehenden Einstellungen
als auch bei einer zu einem späteren Zeitpunkt
erforderlichen Änderung derselben nützlich
sein.
Bei zweischienigen Anlagen mit Haupt- und
Reservestrecken
empfehlen
Inbetriebnah-me
der
beiden
nacheinander vorzunehmen, wobei mit der
Regelstrecke mit tieferem Regeldruck-
Einstellwert,
d.h.
der
Reservestrecke,
begonnen wird. Für diese Regelstrecke
gelten dann natürlich andere Werte als in
den Tabellen 7 und 8 angegeben.
Bevor die Inbetriebnahme des Regelgeräts
erfolgt, ist sicherzustellen, dass alle
Absperr-organe (in Eingangs-, Ausgangs-
und evtl. Bypassleitung) geschlossen sind
und dass die Gastemperatur hoch genug ist,
um
Kondensatbil-dung
temperaturbedingte
Störungen
vermeiden.
5.3
INBETRIEBNAHME DES REGEL-
GERÄTS
Falls an der Regelstrecke ein separates
Sicherheitsabblaseventil vorhanden ist, wird
für dessen Überprüfung auf Abschnitt 3.1
verwiesen.